Statistics


Unit 1 Details

Capacity:    1218 Mwe
Reactor Type:    Westinghouse four-loop pressurized water reactor (PWR)
Reactor Core:    192 fuel assemblies
Reactor Vessel:    40' high 15' wide
Containment Bldg:    Double-dome concrete and steel construction over 5.5' thick.
   219' tall
   140' inside diameter
Turbine:    General Electric 1800 rpm
Generator:    General Electric 22 kV
Architect:    United Engineers and Constructors
Total Investment:    $6 Billion

Safety Design Criteria


Reactor

System operating pressure    2235 psi
Coolant flow rate    402,800 gpm
Coolant inlet temperature    558 degrees F.
Coolant outlet temperature    618 degrees F.
Reactor vessel inside diameter    14' 5"
Reactor vessel height    43' 10"
Reactor Coolant pump HP    7000

Circulating Water System

Flow    450,000 gpm
Pumps    3 at 150,000 gpm
Inlet Tunnel    17,140' long 19' dia.
Exhaust Tunnel    16,483' long 19' dia.
Condensor    3 shell, double pass, 754,110 sq. ft
CW temp    55 degrees F.
Temperature rise    34 degrees F. - 5 degrees after discharge into ocean

Materials

Structural Concrete    274,914 CY (doesn't include tunnel)
Structural Rebar    34,160 TN (doesn't include tunnel)
Structural Formwork    2,796,747 SF (doesn't include tunnel)
Cadwelds    47,975
Structural Steel    12,168 TN
Small Bore Pipe    151,818 LF
Large Bore Pipe    168,216 LF
Large Bore Welds    19,846
Large Bore Hangers    10,059
Large Bore Valves    2,361
Conduit    641,381 LF
Cable Tray    88,547 LF
Cable Pulling    6,160,931 LF
Cable Terminations    230,705
Tubing    193,669 LF